Reliable Single Interlock Preaction System Manuel de service Page 1

Naviguer en ligne ou télécharger Manuel de service pour Détecteurs de fumée Reliable Single Interlock Preaction System. Reliable Single Interlock Preaction System Technical data Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 10
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model H
Single Interlock
Preaction System
1
1
/
2
” (40mm)
Bulletin 719 Rev. I
Bulletin 719 Rev. I
Instructions for
Installation, Operation,
Care and Maintenance
7 PSI (0.48 bar) Pneumatic Supervising Pressure
with Electric Actuation
Vue de la page 0
1 2 3 4 5 6 7 8 9 10

Résumé du contenu

Page 1 - Care and Maintenance

Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523Model HSingle InterlockPreaction System11/2” (40mm)Bulletin 7

Page 2 - Technical Data

Reliable Automatic Sprinkler Co., Inc.(800) 431-1588 Sales Offices(800) 848-6051 Sales Fax(914) 829-2042 Corporate Officeswww.reliablespri

Page 3 - System Design Considerations

2.General Description Reliable Single Interlock Preaction Systems are designed for water sensitive areas which require protection from inad-vertent wa

Page 4 - - Cont’d

3.Figure 1System Design Considerations The automatic sprinklers, air compressor, releasing devic-es, electric releasing control equipment, fire detect

Page 5 - Preaction Trim Kit

4.Figure 2 — Single Interlock Preaction AssemblySystem Supervising Pressure Requirements - Cont’dIn some circumstances, such as when dry sprinklers a

Page 6 - Maintenance

5.Figure 3 — Single Interlock Preaction, Component IdentificationSystem Operation To activate a Reliable Single Interlock System, two inde-pendent eve

Page 7 - Causing Water Flow

6.Single Interlock Riser Installation The recommended sequence of installation is as follows (refer to Figures 2 and 3): 1. Install the Deluge Riser

Page 8 - Ordering Information

7.Resetting Single Interlock System Refer to Figure 3. 1. Close the valve controlling water supply to the riser assembly and shut off the system air

Page 9

8.Ordering InformationSpecify (Ref. Figure 4):Item No.Component Part Mfr. Description Technical Bulletin1 Deluge Riser Assembly B Model H 5072 Preacti

Page 10 - (800) 848-6051 Sales Fax

9.Installation Dimensions in Inches

Commentaires sur ces manuels

Pas de commentaire